Parameter
No.
Function name Monitor or Data Range
Default
data
Setting
during
RUN
Unit Page
H94
1st Cumulative Motor
Run T
ime
0 to 9,999 (in 10 hours)
0 -
10
hex
page
7-93
H95
DC Injection Braking
Start Characteristic
Selection
0: Slow response
1: Quick response
1
Availa-
ble
-
page
7-63
H96
STOP Key Priority/
Start Check Function
0: Disable STOP key priority,
disable start check function
1: Enable STOP key priority,
disable start check function
2: Disable ST
OP key priority,
enable start check function
3: Enable STOP key priority,
enable start check function
0
Availa-
ble
-
page
7-80
H98
Protection/Mainte-
nance Function Mode
Selection
Bit7: Reserved
Bit6: Braking transistor error
detection
0: Disable
1: Enable
Bit5: Detect charge register
overheat
0: Enable
1: Disable
Bit4: Judge main circuit capac-
itor life
0: Disable
1: Enable
Bit3: Main circuit capacitor life
judgment selection
0: Factory default standard
1: User measurement value
standard
Bit0 to 2: Reserved
80
Availa-
ble
-
page
7-157
H99
Password 2 Setting/
Verification
0000 to FFFF Hex
0
Availa-
ble
-
page
7-77
H114
Anti-regenerative Con-
trol Level
0.0 to 50.0 %
999: Auto
32767
Availa-
ble
%
page
7-85
H130 Do not use - - - - -
4 Parameter List
4-123
M1 Series Standard Type User's Manual (I669)
4-2 List of Parameters by Group
4
4-2-5 Parameter H (High Level Functions)