Parameter
No.
Function name Monitor or Data Range
Default
data
Setting
during
RUN
Unit Page
H131 Do not use - - - - -
H133 Do not use - - - - -
H134 Do not use - - - - -
H147
Speed Control Jog-
ging Feed Forward
Gain
0.00 to 99.99 s
0
Availa-
ble
s
page
5-60
H154
Torque Bias Function
Selection
0: Invalid
1: Operator (H155 to H157)
2: Analog input
4: RS-485 communication
5: Fieldbus (Reserved)
0 - -
page
6-33
H155 Torque Bias Level 1
-300 to +300 %
0
Availa-
ble
%
page
6-33
H156 Torque Bias Level 2
-300 to +300 %
0
Availa-
ble
%
page
6-33
H157 Torque Bias Level 3
-300 to +300 %
0
Availa-
ble
%
page
6-33
H158
Torque Bias Mechani-
cal Loss Compensa-
tion
0 to 300 %
0
Availa-
ble
%
page
6-33
H159
Torque Bias Startup
Timer
0.00 to 1.00 s
0 - s
page
6-33
H161
Torque Bias Shutdown
T
imer
0.00 to 1.00 s
0 - s
page
6-33
H162 Torque Bias Limit
0 to 300 %
200 - %
page
6-33
H173
Magnetic Flux Level at
Light Load
10 to 100%
100
Availa-
ble
%
page
7-150
H180
Brake Error Detection
T
ime
0.00 to 10.00 s
1.00
Availa-
ble
s
page
6-76
4 Parameter List
4-124
M1 Series Standard Type User's Manual (I669)