Appendix BSpecifications
156
Terminal Connections
I/O word “m” I/O word “m+1”
0
1
1
2
2
3
3
4
4
5
5
6
6
7
7
8
COM
9
A
24 VDC
0
1
1
2
2
3
3
4
4
5
5
6
6
7
7
8
COM
9
B
+
+
24 VDC
8
10
9
11
10
12
11
13
12
14
13
15
14
16
15
17
COM
18
8
10
9
10
11
12
13
14
15
COM
+
+
24 VDC 24 VDC
11
12
13
14
15
16
17
18
NC
19
NC
20
NC
19
NC
20
Note 1. I/O word “m” is determined by the I/O number setting (m = IR 030 + 2 × I/O number).
2. The power can be supplied in either polarity, but the same polarity must be used for all COM terminals.
Connect power supply wiring to every COM terminal, even though the COM terminals are connected
internally.
DC Input Unit C200H-ID217 (64 Points)
Rated Input Voltage 24 VDC
Operating Input Voltage 20.4 to 26.4 VDC
Input Impedance
5.6 kW
Input Current 4.1 mA (at 24 VDC)
ON Voltage 14.4 VDC min.
OFF Voltage 5.0 VDC max.
ON Response Time 1.0 ms max.
OFF Response Time 1.0 ms max.
No. of Circuits 2 (32 points/common)
All 64 points cannot be turned ON simultaneously
at high temperatures. Refer to the following graph.
Internal Current Consumption 120 mA 5 VDC max.
Weight 250 g max.
Dimensions D-shape