EasyManua.ls Logo

Omron C200HX Series

Omron C200HX Series
241 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
84
5-1 Troubleshooting
CPU Racks and Expansion I/O Racks
Error Probable cause Possible correction
POWER indicator does not light.
The voltage selector terminal setting is
wrong. (A 100-VAC voltage is used
when set to 200 VAC.)
Correct the voltage selector terminal
setting.
The 24-V output terminals are
externally shorted.
Correct the wiring.
An internal fuse has blown.
The Power Supply Unit is broken. (A
200-VAC voltage was used when set
to 100 VAC.)
Replace the Power Supply Unit.
There is a short-circuit in the internal
power supply. (There is a short-circuit
in the 5/26-VDC supplied by the
Power Supply Unit in a Unit on the
Rack.)
Replace the Unit with the short-circuit.
RUN indicator does not light. The program has an error (no END
instruction).
Correct the program.
A power supply line is defective. Replace the CPU Unit.
Special I/O Units are assigned
overlapping unit numbers.
Correct the unit number assignments.
A Slave Unit’s power supply is turned
off, or no Unit is set as the terminator.
Turn on the power to the Slave Unit,
or set a Unit as the terminator.
RUN indicator is lit, but RUN output
does not turn on.
The power circuit is defective. Replace the CPU Unit.
Relays do not operate from a
particular number onwards.
The I/O bus is defective. Replace the Backplane.
Outputs (or inputs) turn ON for
particular Relay numbers.
All the bits from a particular Unit turn
ON.
Troubleshooting Section 5-1

Table of Contents

Other manuals for Omron C200HX Series

Related product manuals