8
Initialization method
 
8.  Initialization method 
 
The setting procedures in this document are based on the factory default settings.   
Some settings may not be applicable unless you use the devices with the factory default 
settings. 
 
8.1.  Initializing PLC 
To initialize the settings of PLC, it is necessary to initialize Serial Communications Unit and 
CPU Unit. Change the operating mode of PLC to PROGRAM mode before the initialization. 
 
8.1.1.  Serial Communications Unit 
To initialize the settings of Serial Communications Unit, select Edit - I/O Table and Unit 
Setup from the PLC Menu in CX-Programmer and perform the following steps.   
(1)Right-click Serial Communications Unit in the PLC IO Table Window and select Unit Setup 
from the menu.   
 
(2)In the CJ1W-SCU42 [View Parameters] Dialog Box, click Set Defaults first, then click 
Transfer[PC to Unit].