Regulations and Standards
Conformance to EU Directives
Applicable Directives
EMC Directives
Concepts
EMC Directives
OMRON devices that comply with EU Directives also conform to the related EMC standards so that
they can be more easily built into other devices or the overall machine. The actual products have
been checked for conformity to EMC standards.*1
Whether the products conform to the standards in the system used by the customer, however, must
be checked by the customer. EMC-related performance of the OMRON devices that comply with
EU Directives will vary depending on the configuration, wiring, and other conditions of the equip-
ment or control panel on which the OMRON devices are installed. The customer must, therefore,
perform the final check to confirm that devices and the overall machine conform to EMC standards.
*1. Applicable EMC (Electromagnetic Compatibility) standards are as follows: EMS (Electromagnetic Suscept-
ibility): EN61326 EMI (Electromagnetic Interference): EN61326 (Radiated emission: 10-m regulations).
Conformance to EU Directives
The CK3E-series comply with EU Directives. To ensure that the machine or device in which the
CK3E-series Controllers are used complies with EU Directives, the following precautions must be
observed.
The CK3E-series Units must be installed within a control panel.
You must use double or reinforced insulation power supply for the DC power supplies that are
connected as the Unit power supplies for the CK3E-series.
We recommend that you use the OMRON S8JX-series Power Supplies. EMC standard compli-
ance was confirmed for the recommended Power Supplies.
CK3E-series that comply with EU Directives also conform to the Common Emission Standard
(EN61326). Radiated emission characteristics (10-m regulations) may vary depending on the
configuration of the control panel used, other devices connected to the control panel, wiring, and
other conditions.
You must therefore confirm that the overall machine or equipment in which the CK3E-series are
used complies with EU Directives.
This is a Class A product (for industrial environments). In a residential environment, it may cause
radio interference. If radio interference occurs, the user may be required to take appropriate
measures.
Attach the clamp core to the Ethernet communications cable. Refer to Recommended Clamp
Core and Attachment Procedure on page 4-20 for details of the procedure to attach the clamp
core.
Regulations and Standards
23
CK3E-series Programmable Multi-Axis Controller Users Manual Hardware (I610)

Table of Contents

Other manuals for Omron CK5M-CPU 1 Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Omron CK5M-CPU 1 Series and is the answer not in the manual?

Omron CK5M-CPU 1 Series Specifications

General IconGeneral
BrandOmron
ModelCK5M-CPU 1 Series
CategoryController
LanguageEnglish

Related product manuals