8 - 17
8 Troubleshooting and Maintenance
E3NW-ECT EtherCAT Digital Sensor Communication Unit Operation Manual (E429)
8-1 Troubleshooting
8
8-1-6 Application Layer Status Codes
002C hex
Synchronization
Error
The SYNC0 interrupt
stopped during operation
in Operational state.
Not
saved
Can be
notified
Check the
synchronization settings.
(Encoder Input Slave
Units only)
002D hex
SYNC Signal
Not Received
No SYNC0 signals have
been received since
entering DC mode.
Not
saved
Can be
notified
Check the
synchronization settings.
(Encoder Input Slave
Units only)
AL status
code
Name of error Contents
Diagnosis
history
Notification
to EtherCAT
Master Unit
Measures