16
Communications Function Section 1-4
Note The Protocol Setting parameter is displayed only when CompoWay/F commu-
nications are being used.
Setting Communications
Data
Match the communications specifications of the E5CN/AN/EN/GN and the
host computer. If a 1:N connection is being used, ensure that the communica-
tions specifications for all devices in the system (except the communications
Unit No.) are the same.
Parameter name Symbol Setting (monitor) value Selection symbols Default Unit
Protocol Setting psel CompoWay/F (SYSWAY),
Modbus
cwf, mod CompoWay/F
(SYSWAY)
None
Communications
Unit No.
u-no 0 to 99 1 None
Communications
Baud Rate
bps 1.2, 2.4, 4.8, 9.6, 19.2,
38.4, 57.6
1.2, 2.4, 4.8, 9.6, 19.2, 38.4.
57.6
9.6 kbps
Communications
Data Length
len 7, 8 7 Bits
Communications
Stop Bits
sbit 1, 2 2 Bits
Communications
Parity
prty None, Even, Odd none, even, odd Even None
Send Data Wait
Time
sdwe 0 to 99 20 ms