6 - 69
6 Parameters
E5@C Digital Temperature Controllers User’s Manual (H174)
6-8 Advanced Function Setting Level
6
mav
Moving Average Count
This parameter sets the number of inputs to include in the moving average. The data after
moving average processing is illustrated in the following figure.
Use a moving average to suppress rapid changes in the input.
pmav
FB Moving Average Count
Position-proportional Models
You can set the moving average count for the FB input. The data after moving average
processing is illustrated in the following figure.
Use a moving average to suppress rapid changes in the FB input.
You can use this parameter only with the E5EC-PR@-8@@ or E5AC-PR@-8@@. (The
Digital Controller must be manufactured in August 2014 or later (version 2.2 or higher).)
Function
Input data
Operation result
Time
Setting
*The default is 8 for models other than the E5@C-@-0@.
Setting range Unit Default
OFF, 2, 4, 8, 16, or 32 Times OFF*
800
Function
Input data
Operation result
Time
Setting
Setting range Unit Default
OFF, 2, 4, 8, 16, or 32 Times 16

Table of Contents

Other manuals for Omron E5AC

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Omron E5AC and is the answer not in the manual?

Omron E5AC Specifications

General IconGeneral
Mounting TypePanel Mount
Sampling Period50 ms
Protection structureIP66 (front panel)
Control MethodON/OFF
Input TypeThermocouple, RTD
Supply Voltage100 to 240 VAC
Output TypeRelay, Voltage, Current
Control OutputRelay, voltage, current
Dimensions96 x 96 mm
Display TypeLCD
Number of Displays2
Alarm OutputRelay
CommunicationRS-485
Ambient Operating Temperature-10 to 55°C
Ambient Operating Humidity25% to 85% RH