56
9-1 Engineering Level
To go to engineering level, set pin 4 of the internal function switch of the E5J to
ON before turning the E5J on. After this setting, set pin 4 of the internal func-
tion switch to OFF.
Set pin 4 of the
function switch to
ON.
This display will appear.
Turn on the E5J.
9-2 Engineering Level Parameter List
The following is a list of engineering level parameters.
Display Name Setting range Setting before
shipping
Users remarks
d-U °C/°F selection
c: °C
f: °F
c
LEn Data bit length 7: Data length of 7 bits
8: Data length of 8 bits
7
PrtY Parity check
none: No parity
eUen: Even
odd: Odd
eUen
Sbit Stop bit length 1: 1 bit
2: 2 bits
2
15.0
S.t-b Stable range 0.1 to 999.9 °C/°F 15.0 (27.0)
ALFA Alpha 0.00 to 1.00 0.65
rEt Automatic return of
display mode
0 to 99 s
0: No automatic return
0
rESt Standby sequence reset
method
0: Reset method 0
1: Reset method 1
0
in-S Input shift display
off: Not displayed
on: Displayed
off
ALH1 Alarm 1 hysteresis 0.1 to 999.9 °C/°F 0.2 (0.4)
ALH2 Alarm 2 hysteresis 0.1 to 999.9 °C/°F 0.2 (0.4)
SL-L Set point lower limit
value
Set range lower limit to
set point upper limit
value (see note 1).
(°C/°F)
–200 (–300)
Engineering Level Parameter List
Section 9-2