CompoWay/F
SECTION 2 CompoWay/F Communications Procedures
2-20
(2) Response Code
Normal Completion
Error Occurred
(3) Operation Commands and Precautions
● Communications Writing
Set the Communications Writing parameter to “ON: enabled” or “OFF:
disabled” with the related information setting. The setting can be
accepted in both setup area 0 and setup area 1. An operation error will
occur, however, if enabling or disabling communications writing is set
for an event input.
0C Alarm Latch Cancel 00: Alarm 1 latch cancel
01: Alarm 2 latch cancel
02: Alarm 3 latch cancel
03: HB alarm latch cancel
04: HS alarm latch cancel
05: OC alarm latch cancel
0F: All alarm latch cancel
0E Invert Direct/Reverse
Operation
00: Not invert
01: Invert
11 Program Start 00: Reset
01: Start
Response code Name Description
0000 Normal completion No errors were found.
Response code Error name Cause
1001 Command too long The command is too long.
1002 Command too short The command is too short.
1100 Parameter error Command code and related
information are wrong.
2203 Operation error • The Communications Writ-
ing parameter is set to “OFF”
(disabled). The command is
received regardless of the
Communications Writing
parameter setting (ON/OFF).
• Processing could not be per-
formed. For details, see (3)
Operation Commands and
Precautions below.
• EEPROM error
Command
code
Command content Related Information