Digital Position-Proportional Controllers E5EZ-PRR 45
Operation/ Adjustment Protection
The relationship between the set values and the range of protection is as shown below.
When the set value is 0, there is no protective function.
The initial value is 0.
Initial Setting/ Communications Protection
This protect level restricts movement to the initial setting, communications setting, and
advanced function setting levels
.
Default setting: 1.
Setting Change Protection
Places restrictions on changes to settings with keys.
off
: Able to use unit keys to change settings.
on: Unable to use unit keys to change settings, but this level can be changed.
Automatic/ Manual Key Protection
Initial value is "off".
Setting Communications Parameters
Configures the E5EZ-PRR's communications specifications, so that its communications
with the host computer can be configured properly. In a layout where one point communi-
cates with multiple points, in addition to all of the communication unit numbers, all other
settings should match. Each unit must have a single communication unit number set for it.
Mode
Set Values
: Can be displayed/ changed
: Can be displayed
× : Cannot be displayed/
no changes in level allowed
0123
Present value ❍❍❍❍
Set value
Others × ×
Adjustment level × × ×
Set Value Initial setting level Communications
0
Able to switch (able to switch to the advanced
functions setting level)
Able to switch
1
Able to switch (unable to switch to the advanced
functions setting level)
Able to switch
2 Able to switch Unable to switch
Set Value Automatic/ Manual Operations
off Automatic/ Manual Able to switch
on Automatic/ Manual Unable to switch
Parameters Character
display
Set
(monitor) value
Setup Initial
value
Unit
Communications
Unit No.
u-no 0 to 99 1 None
Baud rate bps
1.2,
2.4, 4.8,
9.6,
19.2
1. 2,
2. 4,
4. 8,
9. 6
19. 2
9.6 Kbps
Data bits len 7,
8 7 Length
Stop bits sbit 1,
2 2 Bit
Communication
parity
prty None, even, odd
none,
even
odd
Even None
oapt
0
icpt
1
wtpt
off
keyp
off
Protect level
Operation /
adjustment protection
Initial setting /
communications
protection
Setting change protection
Automatic/ manual
key protection
l.prt
l.prt
l.prt
l.prt
u-no
1
len
7
sbit
2
Communications setting level
Communications
Unit No.
Baud rate
Data bits
Stop bits
Communication parity
bps
96
l.com
l.com
l.com
l.com
l.com

Other manuals for Omron E5CZ

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Omron E5CZ and is the answer not in the manual?

Omron E5CZ Specifications

General IconGeneral
Display Type7-segment digital display
Dimensions48 x 48 x 78 mm
Number of Control Outputs1
Ambient Operating Temperature-10 to 55°C
Control MethodPID control, ON/OFF control
Input TypeThermocouple, RTD
Supply Voltage100 to 240 VAC
Output TypeRelay, Voltage, Current
Alarm Output1 or 2 (depending on model)
Setting Resolution0.1 or 1 (depending on input type)
Protection RatingIP20
Ambient Operating Humidity25% to 85% RH (non-condensing)

Related product manuals