For grounding, use a dedicated ground wire (2 mm
2
or larger) and apply Class D grounding
(third class grounding: 100
Ω or less grounding resistance).
Do not share the Sensor controllers ground with other equipment or ground the Sensor con-
troller to the metal structure of a building. Doing so may worsen operation. Whenever possi-
ble, use an independent ground (with the ground pole separated by a minimum of 10 m from
any other ground pole).
Ground to 100 Ω or less, and if possible use a separate ground from those of other devices.
(Refer to figure (a) in the diagram below.)
If using an independent ground is not possible, then use a common ground as shown in fig-
ure (b). Connect to the ground pole of the other device.
Sensor Controller Sensor Controller Sensor Controller
(a) Independent grounds:
Best
Grounding Methods
Other
device
Ground of
100 Ω or less
Other
device
Other
device
(b) Common ground:
Acceptable
(c) Common ground:
Incorrect
3 Insert the terminal block connector (male) to the terminal block connector (female) of Sensor
Controller
.
4 Tightens and fix the left and right screws for the terminal block connector (male). (Recommend-
ed tightening torque: 0.7 to 0.8 N•m)
Terminal block connector (female)
Terminal block connector (male)
5 Setup and Wiring
5-7
FH Series Vision System Hardware Setup Manual (Z366-E1)
5-3 Sensor Controller Installation
5
5-3-2 FH-1000/2000/3000/5000 Series