G9SA
Expansion Units with OFF-delay Outputs
The Expansion Unit connects to a G9SA-301, G9SA-501, G9SA-321, or G9SA-TH301.
Note: The following 15-step OFF-delay time settings are available:
T075: 0.5, 1, 1.5, 2, 2.5, 3, 3.5, 4, 4.5, 5, 5.5, 6, 6.5, 7, and 7.5 s
T15: 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14, and 15 s
T30: 2, 4, 6, 8, 10, 12, 14, 16, 18, 20, 22, 24, 26, 28, and 30 s
Model Number Structure
Model Number Legend
1. Function
None: Emergency stop
EX: Expansion Unit
TH: Two-hand Controller
2. Contact Configuration (Safety Output)
0: None
3: 3PST-NO
5: 5PST-NO
3. Contact Configuration (OFF-delay Output)
0: None
2: DPST-NO
3: 3PST-NO
4. Contact Configuration (Auxiliary Output)
0: None
1: SPST-NC
5. Input Configuration (for G9SA-301/501/321)
None: 1-channel or 2-channel input possible
6. OFF-delay Time (Max. setting time)
None: No OFF-delay
T075: 7.5 seconds
T15: 15 seconds
T30: 30 seconds
Main contact form Auxiliary contact OFF-delay time Model Category
3PST-NO SPST-NC 7.5 s G9SA-EX031-T075 3
15 s G9SA-EX031-T15
30 s G9SA-EX031-T30
1 2 3 4 5 6
G9SA-@@@@@@-@@@@
http://www.ia.omron.com/
2
(c)Copyright OMRON Corporation 2007 All Rights Reserved.
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com