Up/Down Counting Meter
K3NC
C-149
Counters
Setting Procedures
The K3NC has four modes: RUN mode for normal operations, Setting mode for initial parameter input, Protect mode for lock-out configuration, and
Maintenance mode for initializing set values. The parameters that are accessible on any individual K3NC will vary depending on the Output Board
installed. Refer to the
K3NC Operation Manual
for details.
RUN Mode: Remains in this mode under normal operation.
The process value can be monitored.
Using the front panel keys, the comparative set value can be changed and counting value reset can be performed.
Setting Mode: Used for making initial settings.
Includes settings for four menus (Set value (
sUset
sUsetsUset
sUset
), prescaling (
pscl
psclpscl
pscl
), setup (
setup
setupsetup
setup
), option (
opt
optopt
opt
)) and the output test.
Protect Mode: Used for locking the front key operation or parameter changes.
Maintenance Mode: Used for initializing set values.
sUset
sUsetsUset
sUset
- Program set values
s.bank
s.banks.bank
s.bank
Select bank no. of set values
sU
sUsU
sU*.01
.01.01
.01
Enter set value OUT1 of bank 1
sU
sUsU
sU*.02
.02.02
.02
Enter set value OUT2 of bank 1
sU
sUsU
sU*.03
.03.03
.03
Enter set value OUT3 of bank 1
sU
sUsU
sU*.04
.04.04
.04
Enter set value OUT4 of bank 1
sU
sUsU
sU*.05
.05.05
.05
Enter set value OUT5 of bank 1
Note:
The above is an example when the bank number is set to 1.
pscl
psclpscl
pscl
- Display prescaling
p.bank
p.bankp.bank
p.bank
Select bank no. of prescale values
ps
psps
ps*.ax
.ax.ax
.ax
Set the mantissa (X) of the prescale value
ps
psps
ps*.ay
.ay.ay
.ay
Set the exponent (Y) of the prescale value
decp.
decp.decp.
decp.*
Select decimal point
Note:
The above is an example when the bank number is set to 1.
setup
setupsetup
setup
- Program input mode/input sensor/serial communications
count
countcount
count
Specify input mode
in
inin
in
Select a sensor type
u-no
u-nou-no
u-no
Enter the unit no. for the host
bps
bpsbps
bps
Select the baud rate
len
lenlen
len
Select the word bit length
sbit
sbitsbit
sbit
Select the stop bits
prty
prtyprty
prty
Select the parity bits
opt
optopt
opt
- Supplementary settings related to display or control
memo
memomemo
memo
Select power failure memory function
compn
compncompn
compn
Set compensation value
con-p
con-pcon-p
con-p
Select conditions that allow compensation input
out
outout
out
Select output mode
lset.h
lset.hlset.h
lset.h
Enter the upper limit (H) of linear output range
lset.l
lset.llset.l
lset.l
Enter the lower limit (L) of linear output range
r-l
r-lr-l
r-l
Select the remote/local programming
test
testtest
test
- Generating simulated input for testing the output function
prot
protprot
prot
- Program lock-out configuration
all
allall
all
Enable all key protection
sUset
sUsetsUset
sUset
Enable set value change prohibition
reset
resetreset
reset
Enable prohibition of counting value reset using the front
panel keys
secr
secrsecr
secr
Specify the menus to be protected against setting in the
setting mode
1 s
1 s
+
+
ESC
ESC
ESC
ESC
Power ON
RUN mode
Setting mode
Maintenance mode
Protect mode
When power is ON