3 Error Tables
3-72
NJ-series Troubleshooting Manual (W503)
64440000 hex Negative
Limit Input
An instruction for a
motion in the nega-
tive direction was
executed when the
negative limit input
was ON.
• An instruction for a motion in
the negative direction was exe-
cuted when the negative limit
input was ON, or an instruction
for a motion with no direction
specification was executed
when the negative limit input
was ON. An axes group motion
control instruction was exe-
cuted when the negative limit
input was ON.
S NJ-series
Motion Con-
trol Instruc-
tions
Reference
Manual (Cat.
No. W508)
74220000 hex Servo Main
Circuits OFF
An attempt was
made to turn ON
the Servo when the
main circuit power
supply to the Servo
Drive was OFF.
• An attempt was made to turn
ON the Servo when the main
circuit power supply to the
Servo Drive was OFF.
S Same as
above.
57220000 hex
(Ver. 1.06)
Actual Posi-
tion Over-
flow/Underflo
w
An instruction was
executed that is not
supported during
an actual position
overflow/underflow.
• An instruction was executed
that is not supported during an
actual position overflow or
underflow.
S Same as
above.
57230000 hex
(Ver. 1.06)
Switch Struc-
ture Track
Number Set-
ting Out of
Range
The value of Track -
Number that is
specified in the
Switches in-out
variable to a motion
control instruction is
out of range.
• The value of the member of the
structure variable that was
specified for the in-out variable
of the instruction is out of
range.
S Same as
above.
57240000 hex
(Ver. 1.06)
Switch Struc-
ture First ON
Position Set-
ting Out of
Range
The value of Fir-
stOnPosition that is
specified in the
Switches in-out
variable to a motion
control instruction is
out of range.
• The value of the member of the
structure variable that was
specified for the in-out variable
of the instruction is out of
range.
S Same as
above.
57250000 hex
(Ver. 1.06)
Switch Struc-
ture Last ON
Position Set-
ting Out of
Range
The value of Last-
OnPosition that
is
specified in the
Switches in-out
vari
able to a motion
control instruction is
out of range.
• The value of the member of the
structure variable that was
specified for the in-out variable
of the instruction is out of
range.
S Same as
above.
57260000 hex
(Ver. 1.06)
Switch Struc-
ture Axis
Direction Out
of Range
The value of Axis-
Direction that is
specified in the
Switches in-out
variable to a motion
control instruction is
out of range.
• The value of the member of the
structure variable that was
specified for the in-out variable
of the instruction is out of
range.
S Same as
above.
57270000 hex
(Ver. 1.06)
Switch Struc-
ture Cam
Switch Mode
Out of Range
The value of Cam-
SwitchMode that is
specified in the
Switches in-out
variable to a motion
control instruction is
out of range.
• The value of the member of the
structure variable that was
specified for the in-out variable
of the instruction is out of
range.
S Same as
above.
57280000 hex
(Ver. 1.06)
Switch Struc-
ture Duration
Setting Out of
Range
The value of Dura-
tion that is specified
in the Switches in-
out variable to a
motion control
instruction is out of
range.
• The value of the member of the
structure variable that was
specified for the in-out variable
of the instruction is out of
range.
S Same as
above.
Event code Event name Meaning Assumed cause
Level
Reference
Maj Prt Min Obs Info