3-143
3 Error Tables
NJ-series Troubleshooting Manual (W503)
3-1 Errors by Source
3
3-1-9 Errors in CJ-series Units
74620000 hex Scan List
Regis-
ter/Clear
Failed
An operating error
occurred when reg-
istering or clearing
the scan list by per-
forming one of the
following opera-
tions.
CPU Unit is not in PROGRAM
mode.
Request processing is not pos-
sible in this status or the
request was made when the
operation was already in prog-
ress. The following are the main
causes of Unit status errors.
A software switch operation
for the master function was
executed when the master
function was disabled.
A switch that can be used
only when the scan list is dis-
abled was used when the
scan list was enabled.
A switch that can be used
only when the scan list is
enables was used when the
scan list was disabled.
A software switch operation
for the slave function was
executed when the slave
function was disabled.
A configuration error has
occurred.
There is an error in the parame-
ters specified in the user set-
tings, and the requested setting
could not be made.
More than one software switch
changed to TRUE at the same
time. Or, another software
switch changed to TRUE before
processing was completed for a
previous software switch.
S CJ-series
DeviceNet
Units Opera-
tion Manual for
NJ-series
CPU Unit (Cat.
No. W497)
74630000 hex Slave Func-
tion
Enable/Dis-
able Failed
An error occurred in
one of the following
operations in the
slave function.
An attempt was made to enable
the slave function when it was
already enabled.
An attempt was made to dis-
able the slave function when it
was already disabled.
CPU Unit is not in PROGRAM
mode.
More than one software switch
changed to TRUE at the same
time. Or, another software
switch changed to TRUE before
processing was completed for a
previous software switch.
S Same as
above.
74640000 hex Slave Fixed
Allocation
Area Setting
Failed
An error occurred in
one of the following
operations for fixed
allocation of the
slave.
The slave function is not dis-
abled.
CPU Unit is not in PROGRAM
mode.
More than one software switch
changed to TRUE at the same
time. Or, another software
switch changed to TRUE before
processing was completed for a
previous software switch.
S Same as
above.
Event code Event name Meaning Assumed cause
Level
Reference
Maj Prt Min Obs Info

Table of Contents

Other manuals for Omron NJ Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Omron NJ Series and is the answer not in the manual?

Omron NJ Series Specifications

General IconGeneral
Program CapacityUp to 128 MB
SD Card SlotYes
Power Supply Voltage24 VDC
Motion ControlYes
USB Ports1
Operating Temperature0°C to 55°C
Communication InterfacesEthernet/IP, EtherCAT, USB
Safety FunctionOptional
Storage Temperature-20°C to 75°C
Communication PortsUSB
DimensionsVaries by model
WeightVaries by model