3 Error Tables
3-18
NJ-series Troubleshooting Manual (W503)
54010413 hex Undefined CJ-
series Memory
Address
The required specification
is missing for a variable for
which CJ-series Unit mem-
ory must be specified.
The required AT speci-
fication is missing for a
variable for which CJ-
series Unit memory
must be specified.
S NJ-series
Instruc-
tions Ref-
erence
Manual
(Cat. No.
W502)
54010414 hex Stack Underflow There is no data in a stack. An attempt was made
to read data from a
stack that contains no
data.
S Same as
above.
54010416 hex Illegal Number of
Array Elements or
Dimensions
The valid range was
exceeded for the number of
array elements or dimen-
sions in an array I/O param-
eter for an instruction.
The valid range was
exceeded for the num-
ber of array elements
or dimensions in an
array I/O parameter for
an instruction.
S Same as
above.
54010417 hex Specified Task
Does Not Exist
The task specified for the
instruction does not exist.
The specified task
does not exist.
S Same as
above.
54010418 hex Unallowed Task
Specification
An unallowed task was
specified for an instruction.
The local task, the pri-
mary periodic task, or
a periodic task was
specified.
S Same as
above.
54010419 hex Incorrect Data
Type
A data type that cannot be
used for an instruction is
specified for an input or in-
out variable.
A data type that can-
not be used for an
instruction is specified
for an input or in-out
variable.
S Same as
above.
5401041A hex Multi-execution of
Instructions
Multi-execution was speci-
fied for an instruction that
does not support it.
Execution of an
instruction that does
not support multi-exe-
cution of instructions
was specified more
than once.
S Same as
above.
5401041B hex
(Ver. 1.02)
Data Capacity
Exceeded
Processing was not possi-
ble because the data that
was passed to the instruc-
tion was too large.
Data that exceeded
the size that can be
processed was
passed to an instruc-
tion.
S Same as
above.
5401041C hex
(Ver. 1.04)
Different Data
Sizes
The size of the data speci-
fied for instruction input or
in-out data is different from
the siz
e of the target
paramete
r.
Data of a size that is
different from the size
of the target parame-
ter was specified for
the input or in-out data
of an instruction.
S Same as
above.
5401041D hex
(Ver. 1.05)
Exceeded Simulta-
neous Instruction
Executed
Resources
The maximum resources
that you can use for the rel-
evant instruction group at
the same time was
exceeded.
More than the maxi-
mum number of rele-
vant instructions were
executed at the same
time. The maximum
number of instruc-
tions for the relevant
instruction group is as
follows:
DB connection
instructions: 32
S Same as
above.
54010800 hex FINS Error An error occurred when a
FINS command was sent
or received.
An error occurred
when a FINS com-
mand was sent or
received.
S Same as
above.
54010801 hex FINS Port Already
in Use
The FINS port is being
used.
The FINS port is being
used.
S Same as
above.
Event code Event name Meaning Assumed cause
Level
Refer-
ence
Maj Prt Min Obs Info

Table of Contents

Other manuals for Omron NJ Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Omron NJ Series and is the answer not in the manual?

Omron NJ Series Specifications

General IconGeneral
Program CapacityUp to 128 MB
SD Card SlotYes
Power Supply Voltage24 VDC
Motion ControlYes
USB Ports1
Operating Temperature0°C to 55°C
Communication InterfacesEthernet/IP, EtherCAT, USB
Safety FunctionOptional
Storage Temperature-20°C to 75°C
Communication PortsUSB
DimensionsVaries by model
WeightVaries by model