5 Troubleshooting
5-50
NJ-series CPU Unit Hardware User’s Manual (W500)
* For details, refer to I/O Operation for Major Fault Level Controller Errors on page 5-6.
* For details, refer to I/O Operation for Major Fault Level Controller Errors on page 5-6.
Event name I/O Setting Check Error Event code 34010000 hex
Meaning There is an inconsistency between a Unit model in the Unit Configuration in the CPU Unit and the Unit model that is
mounted in the Controller.
Source PLC Function Module Source details I/O bus master Detection
timing
At power ON,
Controller reset,
or Unit Configura-
tion and Setup
transfer
Error attributes Level Major fault Recovery Cycle the power
supply or reset
the Controller.
Log category System
Effects User program Stops. Operation Stops.*
System-defined
variables
Variable Data type Name
None --- ---
Cause and
correction
Assumed cause Correction Prevention
A Unit model or Special Unit unit num-
ber in the Unit Configuration in the
CPU Unit is different from the Unit
model or the Special Unit unit number
of the Unit that is mounted in the Con-
troller.
Correct the Unit Configuration in the
CPU Unit or the physical Unit configu-
ration so that there are no inconsis-
tencies.
Make sure that the Unit Configuration
in the CPU Unit and the physical Unit
configuration are consistent.
Attached
information
Attached information 1: The lowest slot number where an error was detected on the CPU Rack: 0 to 9, When the CPU
Rack is normal: 10
Attached information 2: The lowest slot number where an error was detected on Expansion Rack 1: 0 to 9, When
Expansion Rack 1 is normal: 10
Attached information 3: The lowest slot number where an error was detected on Expansion Rack 2: 0 to 9, When
Expansion Rack 2 is normal: 10
Attached information 4: The lowest slot number where an error was detected on Expansion Rack 3: 0 to 9, When
Expansion Rack 3 is normal: 10
Precautions/
Remarks
None
Event name PLC Function Processing Error Event code 44400000 hex
Meaning A fatal error was detected in the PLC Function Module.
Source PLC Function Module Source details I/O bus master Detection
timing
Continuously
Error attributes Level Major fault Recovery Cycle the power
supply.
Log category System
Effects User program Stops. Operation Stops.*
System-defined
variables
Variable Data type Name
None --- ---
Cause and
correction
Assumed cause Correction Prevention
An error occurred in the software. Contact your OMRON representative. None
Attached
information
Attached information 1: System information
Attached information 2: System information
Attached information 3: System information
Attached information 4: System information
Precautions/
Remarks
None