3-45
H Setting Pn600 (Regeneration Resistor Capacity) for an External
Regeneration Resistor
Pn600 (Regeneration Resistor Capacity) must be set correctly when using an external regeneration
resistor. The regenerative energy in the Servo Driver is calculated based on the assumption that the
regeneration resistance that is built into the Servo Driver is connected. The following settings are there-
fore recommended for Pn600 (Regeneration Resistor Capacity).
Servo Driver model External
regeneration
resistance (W)
Absorption
capacity of
external
regeneration
resistor (W)
Regeneration
resistance built
into Servo Driver
(W)
Recommended
setting for Pn600
R88D–WT05H/08H/10H
47 70 50 7