EasyManua.ls Logo

Omron S82K

Omron S82K
20 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
S82K
S82K
5
Specifications Table – continued from previous page
Item
Non–PFC models PFC model
Single output Dual
outputs
Single output
3 W 7.5 W 7.5 W 15 W 30 W 50 W 90 W 100 W 240 W 240 W
Addi-
tional
func-
tion
Overload
protection
105% to 160%
of rated load
current, auto-
matic reset
(see note 4)
105%
to
250%
of rated
load
current,
auto-
matic
reset
105% to 160% of rated load
current, automatic reset
101%
to
111%
of rated
load
current,
auto-
matic
reset
(see
note 5)
105% to 160% of rated load cur-
rent, automatic reset
Overvoltage
protection (see
note 6)
No S82K-
24024T
model
only
No
Undervoltage
alarm indicator
(DC LOW indica-
tor)
Yes (color: red) S82K-
24024T
model
only
No
Undervoltage
alarm output (DC
LOW output)
No Yes S82K-
24024T
model
only
No
Parallel operation Impossible Possible (2 units max.)
(This table continues on the next page.)
Note: 1. Defined with a 100% load and the rated input voltage (100 or 200 VAC).
2. The output specification is defined at the power supply output terminals.
3. The settings for the output voltage must be within the following range:
+V: ±1% of the rated value
–V: ±5% of the rated value
4. When using the 7.5-W single-output models within the input voltage range between 90 and 110 VDC, the protection function will
operate at a current of 95% to 160% of the rated load current.
5. When the ambient temperature exceeds 25°C, the overload protection function will operate at a current of 92% to 111% of the
rated load current.
6. Circuit-breaker type. To reset, turn the input power supply OFF, then after 1 min has elapsed, turn the input power supply ON
again.

Other manuals for Omron S82K

Related product manuals