What to do if Omron Power Supply dielectric strength test result is NG?
- MMelissa GutierrezSep 7, 2025
If the result of the Omron Power Supply dielectric strength test is NG, it could be due to a few reasons. An impulse may have occurred damaging the Power Supply when the dielectric strength was applied or shut off using a switch or other means. Either gradually change the applied dielectric strength using a variable resistor or apply voltage at zero cross (applied from 0 V). Also test using the dielectric strength value specific to each Product. Finally, if the inspection was conducted with the short bar connected between the ACG and PE terminals, remove the short bar from between the ACG and PE terminals (on applicable models), and then test the dielectric strength and insulation resistance.