S8VS
35
Increase the output voltage setting of Power Supply A and Power
Supply B by the drop in the forward voltage (V
F) of diodes D1 and
D2.
Also, the diodes will cause a power loss equivalent to the Power
Supply output current (I
OUT) times the diode forward voltage (VF).
Therefore, cooling measures must be implemented so that the
temperature of the diodes decreases to the catalog value or lower.
Because of the load power and power loss due to the diodes, do
not exceed the rated power of one Power Supply (rated output
voltage x rated output current).
In Case There Is No Output Voltage
The possible cause for no output voltage may be that the overcurrent
or overvoltage protection has operated. The internal protection may
operate if a large amount of surge voltage such as a lightening surge
occurs while turning ON the power supply.
In case there is no output voltage, please check the following points
before contacting us:
Checking overload protected status:
Check whether the load is in overload status or is short-circuited.
Remove wires to load when checking.
Checking overvoltage or internal protection:
Turn the power supply OFF once, and leave it OFF for at least
3 minutes. Then turn it ON again to see if this clears the condition.
Audible Noise at Power ON
(120-W, 180-W, 240-W, and 480-W Models)
A harmonic current suppression circuit is built into the Power Supply.
This circuit can create noise when the input is turned ON, but it will
last only until the internal circuits stabilize and does not indicate any
problem in the Product.
Type: Schottky barrier diode
Dielectric strength (V
RRM): Rated Power Supply output voltage or
higher
Forward current (I
F): Twice the rated Power Supply output
current or higher
In the interest of product improvement, specifications are subject to change without notice.
ALL DIMENSIONS SHOWN ARE IN MILLIMETERS.
To convert millimeters into inches, multiply by 0.03937. To convert grams into ounces, multiply by 0.03527.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Omron S8VS-24024 and is the answer not in the manual?

Omron S8VS-24024 Specifications

General IconGeneral
BrandOmron
ModelS8VS-24024
CategoryPower Supply
LanguageEnglish

Related product manuals