149
Analog Output Units Section 5-5
4. Select the tab page for the output to be adjusted, and click the Adjustment
Button. (At the same time, set the output range again.)
Adjusting the Low Limit 5. Output the value that is equivalent to 0% from the Master Unit. Always per-
form adjustment with the 0% value.
6. Adjust the analog value that is output from the terminal using the Low Limit
slide bar, as shown in the following window. Repeat adjustments until the
correct 0% value is output from the output device. After compensation is
completed, click the Fix lower adjusting Value Button.
7. To return to the default settings, click the Default Setting Button
8. Close the Adjustment Window, return to the General Tab Page, click the
Download Button, and then click the Reset Button to reset the Unit.
9. Click the OK Button to exit.