204
Temperature Input Units Section 6-4
Setting Procedure (Example: DeviceNet Configurator)
1,2,3... 1. In the Network Configuration Window, double-click the icon of the Slice I/O
Terminal that is to be set. Alternatively, right-click the icon and select Pa-
rameters - Edit. The Edit Device Parameters Window will be displayed.
2. Select the Temperature Input Unit to be edited from the I/O Module Tab
Page.
3. Click the Edit Button on the I/O Module Tab Page. The Edit Unit Parame-
ters Window will be displayed.
4. Select the Tab Page for the input where the Zone Count function is to be
set, and select the Comparator Check Box in the Function Choice Area.
85°C
10°C
Counting starts when this
temperature is exceeded.
When the temperature zone is set
to 10°C above the set temperature
(up to 95°C), the function counts
how long the temperature is within
that 10°C zone.
Counting
starts
Temperature
Time
Counting
starts
Counting
stops