219
Temperature Input Units Section 6-4
Note The terminal block temperature stabilization time does not affect the
upper/lower limit adjustment, so the adjustment can be performed immedi-
ately if 30 minutes have passed since the Temperature Input Terminal’s
power was turned ON.
Step
Timing chart Stabilization time
Input Unit’s power supply ON
Wiring for input 1 upper/lower limit
adjustment
Input 1 upper/lower limit adjustment
Change wiring for input 1 bias
compensation
Input 1 bias compensation
Change wiring for input 2
upper/lower limit adjustment
Change wiring for input 2 bias
compensation
Input 2 bias compensation
(End of adjustment)
Wait at least 30 minutes.
(Check whether additional
time is required for devices
such as the STV, DMM,
and ZERO-CON.)
60 minutes min.
60 minutes min.
Temperature
Input Terminal’s
stabilization time
Terminal Block temperature
stabilization time 1 after wiring
is changed.
Terminal Block temperature
stabilization time 2 after wiring
is changed
Input 2 upper/lower limit adjustment