2-4SectionIR and DM Areas
18
For normal mode, set the operation mode switch on the rear panel of the Unit as
shown in the following diagram.
The allocation of IR words and bits is shown in the following table.
I/O Word
Bits
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
Output
(CPU to
n Not used.
Peak value function inputs
(CPU
t
o
Unit)
8 7 6 5 4 3 2 1
Input
(U i
n+1
Input 1 conversion value
p
(Unit to
CPU)
16
3
16
2
16
1
16
0
CPU)
n+2 Input 2 conversion value
n+3 Input 3 conversion value
n+4 Input 4 conversion value
n+5 Input 5 conversion value
n+6 Input 6 conversion value
n+7 Input 7 conversion value
n+8 Input 8 conversion value
n+9
Error code Disconnection detection inputs
16
1
16
0
8 7 6 5 4 3 2 1
Note For the IR word addresses, n = 100 + 10 x unit number.
For Units #A to #F (10 to 15), n = 400 + 10 x (unit number – 10).
Set Values and Stored Values
Item Contents
Peak value function 0: Do not use.
1: Use peak value.
Conversion value 16-bit binary data
Disconnection detection 0: No disconnection
1: Disconnection
Error code Two digits, hexadecimal (00 for no error)
The disconnection detection function can be used when the input signal range is
set for 1 to 5 V (4 to 20 mA).
Input signal range Voltage/current
1 to 5 V 0.3 V max.
4 to 20 mA 1.2 mA max.
Allocation for Normal
Mode

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Omron SYSMAC C200H-AD003 and is the answer not in the manual?

Omron SYSMAC C200H-AD003 Specifications

General IconGeneral
BrandOmron
ModelSYSMAC C200H-AD003
CategoryI/O Systems
LanguageEnglish

Related product manuals