50
Basic Operating Procedure Section 1-9
2. Set the allocated Software Switches.
n = 1500 + 25
× unit number
The enable/disable status for the Serial Gateway is automatically indicated
by the following flag.
3. Set the local network table in the routing tables as required (using CX-Net).
No-protocol Mode
The following example is for the default (standard) communications condi-
tions, with the send delay set to 100 ms, start code included (e.g., @), end
code included (CR + LF), and number of receive bytes set to 100 bytes.
Board
(CS Series only)
Unit
(CS/CJ Series)
Bit Function
1900 n 12 Port 2 Serial Gateway Prohibit Switch (protocol mac-
ros)
0: Serial Gateway not prohibited
1: Serial Gateway prohibited
04 Port 1 Serial Gateway Prohibit Switch (protocol mac-
ros)
0: Serial Gateway not prohibited
1: Serial Gateway prohibited
Board
(CS Series only)
Unit
(CS/CJ Series)
Bit Meaning
Port 1 Port 2 Port 1 Port 2
1909 1919 n+9 n+19 08 Serial Gateway Prohibited Flag
1: Serial Gateway prohibited
1: Serial Gateway not prohibited
Board
(CS Series only)
Unit
(CS/CJ Series)
Bit Setting Meaning
Port 1 Port 2 Port 1 Port 2
D32000 D32010 m m+10 15 0 Start bits: 1 bit
Data length: 7 bits
Parity: Even
Stop bits: 2 bits
Baud rate: 9,600 bps
11 to 08 3 hex No-protocol
D32001 D32011 m+1 m+11 03 to 00 0 hex The baud rate is 9,600 bps when the default
settings are used.
D32002 D32012 m+2 m+12 15 1 Send delay: User-specified
11 to 00 00 hex Send delay setting range: 10 decimal (000A
hex), Unit: 10 ms
D32003 D32013 m+3 m+13 15 1 CTS control 1: Yes
D32004 D32014 m+4 m+14 15 to 08 40 hex Start code: @ (40 hex)
D32005 D32015 m+5 m+15 12 1 Start code: Yes
09 to 08 10 End code: CR + LF
07 to 00 64 hex Number of receive data bytes: 100 bytes