SETTINGS (SET-UP)
D:11 Hysteresis of the temperature
Using this setting, you can adjust the hysteresis (bandwidth) of the temperature control. This is the temperature diffe-
rence required to switch the compressor on and off.
Setting: D:11 = 2 means the hysteresis is 2. This is the default setting.
The hysteresis can be set from 1°C to 4°C in steps of 0.5°C. If, for example, the day temperature is set to 28°C
and the hysteresis to 2°C, the unit will start to cool at 29°C and stop cooling at 27°C. To shorten the hysteresis
effectively, the resting time of the (D:27)
D:12 Minimum adjustable heating temperature
Using this setting, you can change the minimum adjustable heating temperature. The adjustable values in D:12 are:
default = 16°C, max. = 20°C, min. = 10°C.
D:13 Maximum adjustable heating temperature
Using this setting, you can change the maximum adjustable heating temperature. The adjustable values in D:13 are:
default = 35°C, max. = 50°C, min. = 25°C.
D:14 Minimum adjustable cooling temperature
Using this setting, you can change the minimum adjustable cooling temperature. The adjustable values in D:14 are:
default = 16°C, max. = 20°C, min. = 10°C.
D:15 Maximum adjustable cooling temperature
Using this setting, you can change the maximum adjustable cooling temperature. The adjustable values in D:15 are:
default = 35°C, max. = 35°C, min. = 25°C.
D:16 Not applicable
D:17 Anti-freeze protection of the cooling block
Using this setting, you can determine at which temperature the Anti-Freeze alarm of the cooling block is activated.
The settings in D:17 are: default = 0°C, max. = 5°C, min. = -2°C.
D:18 Not applicable
D:19 Not applicable
D:20 Not applicable
D:21 Cooling block too hot
Using this setting, you can determine at which temperature the Cooling block too hot alarm is activated. The settings
in D:21are: default = 4°C, max. = 0°C, min. = 10°C and 1°C. To activate the alarm, the temperature has to be
too high for a certain period of time. The time is determined by D:22. D:21 and D:22 jointly determine when Error
11 is activated.
D:22 Duration of cooling block over heating
Using this setting, you can determine how long it takes before a Cooling block too hot alarm is given. The settings
in D:22 are 30 mins (standard), 40 mins (maximum), 20 mins (minimum).
The temperature level is determined by D: 21. D:21 and D:22 jointly determine when E:11 is activated.
D:23 Temperature compensation of the room temperature sensor
Using this setting, you can calibrate the room temperature sensor. The setting can be changed if the indication on
the display does not correspond with reality. The settings in D:23 are: default = 0°C, max. = 5°C, min. = -5°C
and can be set in 0.5°C increments.
D:24 Temperature compensation of the cooling block temperature sensor
Using this setting, you can calibrate the cooling block temperature sensor. The settings in D:24 are: default = 0°C,
max. = 5°C, min. = -5°C and can be set in 0.5°C increments.