INSPECTION AND MAINTENANCE
D:25 Temperature of compensating refrigerant return outdoor unit
With this option, the temperature sensor can measure the temperature of the return gas to be calibrated from
the outdoor unit. The setting in D:25 is default = 0°C, max. = 5 °C, min. = -5°C and can be set in 0.5°C
increments.
D:26 Temperature compensation of the Dual Room temperature sensor
With this setting, you can calibrate the second room temperature sensor in the Dual Room conguration. The
settings in D:26 are: default = 0°C, max. = 5°C, min. = -5°C and can be set in 0.5°C increments.
D:27 Resting time of the compressor
Using this setting, you can adjust the resting time between Compressor Off and Compressor On.
Setting: D:27 = 15 means the idle time is 15 seconds. This is the default setting. This setting may be used if
the temperature values in the room change too much because of the time that the compressor is in idle mode.
D:28 Not applicable
D:29 Display lighting
Using this option, you can switch the lighting in the display of the remote control on and off. 0 = Automatic
(default)
1 = Always on
D:30 Fan outdoor unit on / off.
This option determines at which Liquid / Return refrigerant temperature the fan(s) of the outdoor unit will switch
on. The default setting is 27°C. The setting can be changed from 23°C to 33°C.
D:31 Waiting time of outdoor unit fan
With this function, the waiting time can be set and then the fan will run on the outdoor unit after the compressor
is switched on. The standard setting is 30 seconds. (3). The time can be changed between 0 and 90 se-
conds,. (0 to 9). In case of high ambient temperatures, it may be desirable to change the time to 10 seconds,.
In case of cold outdoor temperatures, the setting should be 30 seconds.
D:32 Outdoor air temperature too high.
Standard setting is 40°C. The setting can be changed from 35°C to 45°C
D:33 Temperature of compensating intake (warm) air
Standard setting is 0°C. The setting can be changed from -5°C to +5°C.
D:34 Temperature of compensating outlet (cold) air
Standard setting is 0°C. The setting can be changed from -5°C to +5°C
D:35 Temperature of compensating refrigerant low pressure side
Standard setting is 0°C. The setting can be changed from -5°C to +5°C
D:36 Temperature of compensating outdoor air temperature sensor
Standard setting is 0°C. The setting can be changed from -5°C to +5°C
D:37 Buzzer on / off.
0=off / 1=on