Connecting
17
4. Connecting the I/O signals (CN5)
Connect the input signals and output signals to CN5.
Connection method
Lead wire
Screwdriver
Applicable lead wire
Lead wire size: Stranded wire AWG24 to 18 (0.2 to 0.75 mm
2
)
Conductive material: Use only copper wires.
10 mm
(0.39 in.)
Applicable crimp terminal
Manufacturer: PHOENIX CONTACT GmbH & Co. KG
Model: AI 0,25-10 [Conductor cross-sectional area: 0.14 - 0.34 mm
2
(AWG24)]
AI 0,34-10 [Conductor cross-sectional area: 0.14 - 0.34 mm
2
(AWG22)]
AI 0,5-10 [Conductor cross-sectional area: 0.40 - 0.65 mm
2
(AWG20]
AI 0,75-10 [Conductor cross-sectional area: 0.65 - 0.82 mm
2
(AWG18)]
Connector model: DFMC1,5/9-ST-3,5
(PHOENIX CONTACT GmbH & Co. KG)
Pin assignment
Pin
No.
Signal
name
Function
*1
Description
10
11
12
13
14
15
16
17
18
1
2
3
4
5
6
7
8
9
1 IN-COM0
Input signals common
(for external power supply)
Connect when using an external power supply.
2 IN0 [FWD] The motor rotates in the forward direction while this signal is being ON.
3 IN1 [REV] The motor rotates in the reverse direction while this signal is being ON.
4 IN2 [STOP-MODE]
Select how to stop the motor. When it is OFF, the motor decelerates to a
stop.
5 IN3 [M0]
Select a desired operation data number by switching the ON-OFF status
of the M0 and M1 inputs.
6 IN4 [M1]
7 IN5 [ALARM-RESET] Reset the alarm presently generated.
8 IN6 [MB-FREE]
*2
Select how the electromagnetic brake would operate (hold/release) when
the motor stops.
If this signal is turned ON, the electromagnetic brake can be released.
9 IN-COM1
0 V
(for internal power supply)
Connect when using the internal power supply.
10
TH TH
When a regeneration resistor is used, connect the thermostat output of
the regeneration resistor (normally closed). If the regeneration resistor
overheats to turn the thermostat output OFF, the “regeneration resistor
overheat” alarm is generated.
11
12 VH
External analog setting
input
Connect when the rotation speed or torque limiting value is set externally
using an external potentiometer or external DC voltage. (Refer to p.18)
13 VM
14 VL
15 OUT0+
[SPEED-OUT] 30 pulses are output while the motor output shaft makes one revolution.
16 OUT0−
17 OUT1+
[ALARM-OUT] This signal will be output if an alarm is generated. (Normally closed)
18 OUT1−
*1
Signals in brackets [ ] are functions assigned at the time of shipment. For the pin Nos. 2 to 8 and Nos. 15 to 18, the
assigned function can be changed. Refer to p.24 for signals that can be assigned.
*2
Available for only drivers for electromagnetic brake motor
Input signals circuit
All input signals of the driver are photocoupler inputs.
When an external power supply is used: 20.4 to 28.8 VDC, 100 mA or more
1 k
6.6 k
680
9
1
P
in No.
Photocoupler
2 to 8
0 V
+5 V
z
Changing the logic level setting of input signals
The logic level setting for input terminals IN0 to IN6 can be changed using the
MEXE02
or operation panel.
Refer to the USER MANUAL for details.