EasyManua.ls Logo

Ormazabal cgm.3 system Series - Page 24

Ormazabal cgm.3 system Series
76 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
General instructions
Installation
IG-136-EN version 10; 23/06/2016
24
cgm.3 system
Fully SF6 gas insulated medium voltage switchgear up to 40.5 kV in accordance with IEC Standards
Circuit-breaker function with AV / RAV driving
mechanism
Figure 4.9 Dimensions [mm] of the cable trench for cgm.3-v
with AV / RAV driving mechanism.
Front and rear cable input
or output (D1)
Side cable input or
output (D2)
Trench necessary for the circuit-breaker function with AV / RAV driving mechanism
Cable data
Approximate radius
of curvature*
[mm]
Minimum depth
Cable insulation Cable type
Cable section
[mm
2
]
Cable diameter
[mm]
D1 [mm] D2 [mm]
Height 1400 mm(***)
Dry insulation
Single-core 18/30 kV
< 150 (**) 41 555 750 750
185 43 590
800 800
240 45.2 640
300 47.5 685
850 900
400 48 745
3-core 18/30 kV < 150 92.7 805 1200 1200
Height 1745 mm
Dry insulation
Single-core 18/30 kV
< 150 (**) 41 555 400 400
185 43 590
400 500
240 45.2 640
300 47.5 685
500 600
400 48 745
3-core 18/30 kV < 150 92.7 805 850 850
(*) Check against the data of the manufacturer of the cable used.
(**) 150 mm
2
cable only valid up to 21 kA.
(***) Exclusively for cgm.3-v cubicles .

Table of Contents

Related product manuals