General instructions
Installation
IG-136-EN version 10; 23/06/2016
32
cgm.3 system
Fully SF6 gas insulated medium voltage switchgear up to 40.5 kV in accordance with IEC Standards
Once the cubicle is secured to the floor and the medium
voltage cables are connected, carry out the following
operations to place it in installation position:
1. Release the four screws indicated in Figure 4.27
Figure 4.27 Cable support fastening points
2. Turn the cable support and position it as shown in
Figure 4.28
Figure 4.28 Cable support positioning
3. Position the four M8 screws with their nuts and fasten
until tight.
The cable support is underneath level zero, as shown in
Figure 4.29, prepared for front cable connection:
Figure 4.29 Cable support in cable connection position