17
Standby mode UPS is powered off and no output supply
power, but still can charge batteries.
3-7. Faults Reference Code
Fault event Fault code
Icon Fault event Fault code
Icon
Bus start fail 01 x Inverter voltage Low 13 x
Bus over 02 x Inverter output short 14
Bus under 03 x Battery voltage too high 27
Bus unbalance 04 x Battery voltage too low 28
Inverter soft start fail 11 x Over temperature 41 x
Inverter voltage high 12 x Over load 43
3-8. Warning indicator
Warning Icon (flashing) Alarm
Low Battery
Sounding every second
Overload
Sounding twice every second
Battery is not connected
Sounding every second
Over Charge
Sounding every second
Site wiring fault
Sounding every second
EPO enable
Sounding every second
Over temperature
Sounding every second
Charger failure
Sounding every second
Out of bypass voltage range
Sounding every second