EasyManua.ls Logo

Osaka Smart Box - Page 5

Osaka Smart Box
16 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
OSAKA SMART BOX Simple Manual v1.1 Page 5
Pt 1000 analog inputs (1 KΩ @ 0 °C, 32 °F)
Working range: from -99 to 150 ºC (from -99 to 300 ºF).
Accuracy: ±0.5 % of the full-scale.
Resolution: 0.1 ºC (1 ºF).
Protection: None.
4-20 mA analog inputs
Input’s resistance: ≤ 200 Ω.
Accuracy: ±0.5 % of the full-scale.
Resolution: 0.01 mA.
Protection: None; the maximum current allowed for this
input is 25 mA.
Digital inputs: 3 inputs that can be configured by parameter
by usually open or usually closed contact (open port,
configurable and configurable 2)
5 VDC digital inputs, 2 mA (voltage free)
Power supply: None.
Protection: None.
Digital outputs: up to 6 inputs:
2 SPST electromechanical relays of 30 A resistant to 250
VAC (compressor and fan of the evaporator).
- 2 SPST electromechanical relays of 16 A resistant to 250
VAC (defrosting and ambient light).
- 1 SPST electromechanical relay of 8A resistant to
250VAC (configurable by parameter for anti-fogging
resistance, auxiliary, alarm, port’s resistance, resistants for
the operation in a dead zone, condenser’s fan, compressor
2, defrosting 2, evaporator’s fan 2, liquid valve, on/stand-
by or locked man; configuration by default, condenser0s
fan.
- 1 SPST electromechanical relay of 8A resistant to
250VAC (configurable by parameter for anti-fogging
resistance, auxiliary, alarm, port’s resistance, resistants for
the operation in a dead zone, condenser’s fan, compressor
2, defrosting 2, evaporator’s fan 2, liquid valve, on/stand-
by or locked man; configuration by default, condenser0s
fan.
The device guarantees a reinforced isolation in between
each connector of the digital outputs and the rest of the parts
of the device.
Controller for unipolar stepper electronic expansion
valves: 12 VDC, 260 mA max.
Type 1 or type 2 actions: Type 1.
Additional features of the type 1 or type 2 action: C.
Display: 3 digits display with decimal point and operation
icons.
Communication ports: 1 MODBUS RS-485 port (with
MODBUS communication slave protocol).
Signal and Alarm buzzer: incorporated.