OSAKA SMART BOX Simple Manual v1.1 Page 7
0
7
- - - -
2
Refrigerating gas: 0 = R-22; 1 = R-404A; 2 = R-507A; 3 = R-744; 4 = R-290; 5 = R-717; 6 = R1270; 7 = R-
407F
0
2
- - - -
1
Type of electronic expansion valve: 0 = Generic valve; 1 = Sanhua DPF; 2 = Danfoss ETS 6
0
100
%
30
Opening percentage of the valve during the evaporation temperature probe error (code “pr4”) and/or during
the low pressure probe error (code “pr5”)
0
490
Steps
(pitch) x10
100
Maximum number of steps (pitch) of the generic electronic expansion valve.
0
250
Steps
(pitch)
30
Number of saturation steps (pitch) of the generic electronic expansion valve.
25
999
Steps
(pitch)
100
Frequency of the steps (pitch) of the generic electronic expansion valve.
MIN.
MAX.
U.M.
DEF
COMPRESSOR’S PROTECTIONS
0
240
min
0
Delay in the compressor’s start to the device’s start.
0
240
min
5
Minimum time between two consecutive starts of the compressor.
0
240
min
3
Minimum time of the compressor’s deactivation.
0
240
s
0
Minimum time of the compressor’s activation.
0
240
min
10
Compressor’s activation time during a room temperature’s probe error or an input temperature’s probe error
(code “pr1”).
0
240
min
10
Compressor’s activation time during a room temperature’s probe error or an input temperature’s probe error
(code “pr1”).
0
199
°C/°F (1)
80.0
Superior temperature limit of the condenser in order to activate the condenser superheating alarm (code
COH”).
0
199
°C/°F (1)
90.0
Superior temperature limit of the condenser in order to activate the locked compressor alarm (code “CSd”).
0
15
min
1
Delay of the locked compressor alarm (code “Csd”).
0
999
hx10
0
Limit of working hours of the compressor in order to activate the maintenance request; 0 = Not used
function.
0
240
s
3
Minimum time in between the starts of two different compressors.
0
10
- - - -
2
Number of operation hours of the compressor in order to balance the starts/stops and the number of
working hours in between two compressors.
0
10
- - - -
1
Number of start of the compressor in order to balance the starts/stops and the number of working hours in
between two compressors.
0
2
- - - -
2
Type of compressor’s; 0 = timed, see also u3; 1 = by digital input, see also u3;
2 = by low pressure (only available in model SMART BOX VEX).
MIN.
MAX.
U.M.
DEF
DEFROSTING
0
99
h
8
Interval in between defrostings (0 = defrosting by intervals disabled); or maximum interval of defrosting
(according to the d8 parameter).
0
2
- - - -
0
Type of defrosting; 0 = electric; 1 = hot gas; 2 = compressor stoppage.
-99
99
°C/°F (1)
3.0
End of defrosting temperature.
0
99
min
30
Defrosting’s maximum duration; according to the P3 parameter; (0 = the defrosting is never activated).
0
1
- - - -
0
Defrosting when the device is started (0 = NO; 1 = YES).
0
99
min
0
Minimum time in between the device’s start and the defrosting’s activation; or delay in the activation of the
defrosting at the device’s start (according to the d4 parameter).
0
2
- - - -
1
Visualized temperature during the defrosting; 0 = room temperature or CPT temperature; 1 = “Regulation
Set Point + t”; maximum room temperature or CPT temperature in the activation of the defrosting
(according to the P4); 2 = dEf” indication.
0
15
min
2
Dripping duration.
0
4
- - - -
0
Defrosting mode; 0 = by time intervals; 1 = by compressor start intervals; 2 = by evaporator’s temperature
intervals; 3 = dynamic; 4 = by real time.
-99
99
°C/°F (1)
0.0
Superior temperature limit of the evaporator in order to stop counting the interval’s time in between
defrostings.
0
1
- - - -
0
Enable the alarm of end of defrosting due to maximum time (code “dFd”; 0 = NO; 1 = YES)
0
99
min
0
Minimum time from the compressor’s start to the activation of the defrosting in order for it to be activated
(only if d1 = 1)
0
99
min
0
Pre-dripping duration. (9)
0
999
min
40
Defrosting’s interval; (0 = the function isn’t used).
0
40
°C/°F (1)
3.0
Inferior temperature limit of the evaporator in order to activate the defrosting.
0
500
min
180
Defrosting’s start due to the continual operation of the compressor (0 = the function isn’t used). (10)
0
500
min
200
Minimal duration of consecutive starts of the compressor after the device is turned on and after the turbo
operation mode is activated, which causes the defrosting’s activation (0 = the function isn’t used).