OSB
Series 2 Oil-Fired Steam Boilers – Boiler Manual
Part Number 550-110-772/0816 21
Before operating boiler: Annual service
1. Followstepsunder“Fillthesystem”,page15.
2. Followstepsunder“Tipsforsteamsystems”,page15.
3. Skimtheboilerfollowing“Skimsteamboiler:”,page15.
10 Service and maintenance continued
To place boiler in operation:
Follow information below to prevent severe personal
injury, death or substantial property damage:
• Donotusecrankcasedrainingsoranyoilcontaining
gasoline. See burner manual for proper fuel oil.
• Donotattempttostartburnerwhenexcessoilhas
accumulated in combustion chamber, when unit is
full of vapor, or when combustion chamber is very
hot.
• Donotstartburnerunlesscollectorhood,breeching
and burner mounting door are secured in place.
Never burn garbage or paper in the boiler.
• Neverleavecombustiblematerialaroundboiler.
1. Verifyboilerislledwithwatertoproperlevel.
2. Openburnerdoorandverifyreartargetwall,oorandburner
door insulations are in proper condition and position.
3. Verifyburnermountingdoorisclosedandboltedtightlyand
burner plug is connected.
4. Refer to burner manual for burner start-up, adjustment and
checkout procedures. Factory burner adjustment and settings
may not be suitable for specific job conditions.
Makenalburneradjustmentsusingcombustiontest
equipment to assure proper operation. Do not fire
boiler without water. Sections will overheat, damaging
boiler and resulting in substantial property damage.
5. Check boiler and system piping for leaks.
6. Inspectbreechingandventingforproperoperation.
Boiler relief valve
1. Afterfollowingthewarningdirectionsbelow,ifthereliefvalve
weeps or will not seat properly, replace the relief valve.
Before testing, make certain discharge pipe is
properly connected to valve outlet and arranged to
contain and safely dispose of boiler discharge. Wear
glovestoprotectyourhandsfromhotsurfaces.Verify
that discharge piping is installed in accordance with
this manual and the instructions on the relief valve
tag. Failure to comply will exposeoperator and
others to severe personal injury or death.
SafetyreliefvalvesshouldbereinspectedATLEAST
ONCE EVERYTHREEYEARS, by a licensed
plumbing contractor or authorizedinspection
agency, to ensure that the product has not been
affected by corrosive water conditions and to
ensure that the valve and discharge line have not
been altered or tampered with illegally. Certain
naturally occurring conditions may corrode the valve
or its components over time, rendering the valve
inoperative. Such conditions are not detectable
unless the valve and its components are physically
removed and inspected. This inspection must
only be conducted by a plumbing contractor or
authorizedinspectionagency—notbytheowner.
Failure to reinspect the boiler relief valve as directed
could result in unsafe pressure buildup, which can
result in severe personal injury, death or substantial
property damage.
Check the setting of the boiler limit control. The
control should never be set with a pressure above
10psig.Operatingatahigherpressurecancause
damage to the boiler relief valve.
The boiler relief valve must be tested at least monthly
during the heating season to verify the valve and
discharge piping ow freely. If corrosion and/or
deposits are noticed within the valve body, testing
mustbeperformedmoreoften.A“trylevertest”must
also be performed at the end of any non-service
period.Followtheinstructionsbelowfora“trylever
test”:
• Withthesystematoperatingpressure,liftandhold
the test lever fully open for at least 5 seconds to flush
the valve seat free of sediment and debris. Then
release lever and permit the valve to snap shut.
Review with owner
1. ReviewtheUser’sInformationManualwiththeowner.
2. Emphasizetheneedtoperformthemaintenanceschedule
speciedintheUser’sInformationManual(andinthismanual
aswell).
3. Remind the owner of the need to call in a licensed contractor
shouldtheboilerorsystemexhibitanyunusualbehavior.
4. Remind the owner to follow the proper shutdown procedure
and to schedule an annual start-up at the beginning of the
nextheatingseason.