Fan Type, Number of Set Turbo fan-1 Propeller
Motor Type 6-pole single phase
induction motor
6-pole single
induction
Input kW 0.25 0.25
Rated
Output
kW 0.095 0.055 x
Air-heat Exchanger Slit-fin type Louvre-fin
Refrigerant Control Capillary tube -
Refrigerant Oil (Charged) litre -
Refrigerant (Charged) kg
-
(5.0)
lbs (11.0)
Running
Adjustment
Control Switch Wireless or Wired Remote
Control
-
Room Temperature Thermostat (Main Body) -
Safety Devices Internal protector for compressor, Internal
fan motor, Crankcase heater, High pressure
Current transformer
Noise Level dB Hi 49 Me 46 Lo 43 Hi 58
1. Cooling capacities are based on indoor temperature of 27°C D.B.
(80.6°F D.B.), 19.0°C W.B. (66.2°F W.B.) and outdoor air
temperature of 35°C D.B. (95°F D.B.), 24°C W.B. (75.2°F W.B.)
ELECTRICAL DATA (60Hz)
ITEM / MODEL CS-A50BB4P, CU-C50BBP7
Condition by JIS B 8615
Volts V 220
Phase 3
Power Consumption kW Cool 6.0
Running Current A Cool 17.7
Starting Current A 149
Power Factor % Cool 89
*Power Factor means total figure of compressor, indoor fan motor and outdoor fan motor.
Panasonic Power source AC, 3~220V 60Hz
4.11. CS-A50BB4P / CU-C50BBP8