13.16.2.6 Sunlight Sensor Abnormality
• Abnormality detection:
o When ECONAVI is ON, if the sunlight intensity value below minimum level continuously for 24 hours, the
sunlight sensor disconnection error counter will increase by 1 time. If the ECONAVI is OFF, the 24 hours
timer will be reset, but the sunlight sensor disconnection error counter will not be reset.
• Error Code judgment
o When sunlight sensor disconnection error counter reached 15 times, sunlight sensor is judged as abnormal.
o No ECONAVI indicator blink. Until ECO check code sent during ECONAVI operation ON, the ECONAVI
indicator will blinks.
• When error code happened, the unit is able to operate without sunlight sensor.