42 
11.3.4  Connect the Cable to the Outdoor Unit 
1  Remove the control board cover from the unit 
by loosening the screw. 
2  Connection cable between indoor unit and 
outdoor unit shall be approved 
polychloroprene sheathed 4 x 1.5 mm
2
 
(3/4 ~ 1.5HP) or 4 x 2.5 mm
2
 (2.0HP) flexible 
cord, type designation 60245 IEC 57 or 
heavier cord. Do not use joint connection 
cable. Replace the wire if the existing wire 
(from concealed wiring, or otherwise) is too 
short. Allowable connection cable length of 
each indoor unit shall be 30 mm or less. 
 
 
 
3  Secure the cable onto the control board with 
the holder. 
4  Attach the control board cover back to the 
original position with screw. 
5  For wire stripping and connection requirement, 
refer to instruction 11.2.4.1 of indoor unit. 
 
 
 
 
WARNING
 
   This equipment must be properly earthed. 
 
  Earth wire shall be Yellow/Green (Y/G) in colour 
and longer than other AC wires for safety reason. 
 
 
11.3.5 Piping Insulation 
1  Please carry out insulation at pipe connection portion as mentioned in Indoor/Outdoor Unit Installation 
Diagram. Please wrap the insulated piping end to prevent water from going inside the piping. 
2  If drain hose or connecting piping is in the room (where dew may form), please increase the insulation by 
using POLY-E FOAM with thickness 6 mm or above. 
11.3.6  Cutting and Flaring the Piping 
1  Please cut using pipe cutter and then remove the burrs. 
2  Remove the burrs by using reamer. If burrs is not removed, gas leakage may be caused. Turn the piping end 
down to avoid the metal powder entering the pipe. 
3  Please make flare after inserting the flare nut onto the copper pipes. 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
Terminals on the outdoor unit 1 2 3
Colour of wires
Terminals on the indoor unit 1 2 3
Earth Wire 
longer than 
others AC 
wires for 
safety reason
Terminal 
Board
Holder
Indoor and outdoor 
cable connection
Indoor Unit
When properly fl ared, the internal surface of the 
fl are will evenly shine and be of even thickness. 
Since the fl are part comes into contact with the 
connections, carefully check the fl are fi nish.
 Improper  fl  aring 
Inclined Surface 
damaged
Cracked Uneven 
thickness
1.  To cut 2.  To remove burrs 3.  To fl are
Bar
Red arrow mark
Handle
Core
Yoke
Clamp handle
Bar
0 – 0.5 mm
Copper pipe
Reamer
Point down
Pipe