53 
13.1.4 Compressor Overheating Prevention Control 
  Instructed frequency for compressor operation will be regulated by compressor discharge temperature. The 
changes of frequency are as below. 
  If compressor discharge temperature exceeds 103°C, compressor will be stopped, occurs 4 times per 20 minutes, 
timer LED will be blinking. (“F97” is indicated.) 
 
 
13.1.5  Low Pressure Prevention Control (Gas Leakage Detection) 
  Control start conditions 
o  For 5 minutes, the compressor continuously operates and outdoor total current is between 1.22A and 1.38 A 
(BE25/35TKE), between 0.75A and 0.95A (BE50TKE). 
o  During Cooling and Soft Dry operations: 
Indoor suction temperature - indoor piping temperature is below 4°C. 
o  During Heating operations : 
Indoor piping temperature - indoor suction is under 5°C. 
 Control contents 
o  Compressor stops (and restart after 3 minutes). 
o  If the conditions above happen 2 times within 20 minutes, the unit will: 
 Stop operation 
  Timer LED blinks and “F91” indicated. 
13.1.6 Low Frequency Protection Control 1 
  When the compressor operate at frequency lower than 24 Hz continued for 20 minutes, the operation frequency 
will be changed to 23 Hz for 2 minutes. 
13.1.7 Low Frequency Protection Control 2 
  When all the below conditions comply, the compressor frequency will change to lower frequency. 
 
Temperature, T, for:  Cooling/Soft Dry  Heating 
 Indoor intake air (°C)  T < 14 or T ≥ 30  T < 14 or T ≥ 28 
 Outdoor air (°C)  T < 13 or T ≥ 38  T < 4 or T ≥ 24 
 Indoor heat exchanger (°C)  T < 30  T ≥ 0 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
Frequency
103°C
88°C
Free
OFF
8Hz/45s Down
min A Hz
max B Hz
Comp temp
99°C
87°C
96°C
86°C