Time Delay Safety Control
Anti-Freezing Control
Compressor Reverse Rotation Protection Control
Anti-Dew Formation Control
Automatic Fan Speed Mode
8.2. Soft Dry Mode Operation
The unit starts cooling operation until the room temperature reaches the setting temperature set on the Remote Control, and
then Soft Dry operation will start.
During Soft Dry operation, the Indoor Fan will operate at SLo speed.
Once room temperature reaches below Soft Dry OFF temperature. Indoor Fan, Compressor and Outdoor Fan stop for 6
minutes.
Once the compressor stops, it will not start for 3 minutes during Cooling operation.
Same as Anti-Freezing Control for Cooling Mode operation. (For Soft Dry region, 6 minutes waiting is valid during compressor
stops.)
Same as Compressor Reverse Rotation Protection Control for Cooling Mode Operation. (For Soft Dry region, 6 minutes waiting
is valid during compressor stops.)
Same as Anti-Dew Formation Control for Cooling Mode operation.
When Automatic Fan Speed is selected at Remote Control during Soft Dry operation.
Fan speed off and on at SLo speed.
Deodorizing Control.
21
CS-C18BKP CU-C18BKP5 / CS-C18BKP CU-C18BKP6 / CS-C24BKP CU-C24BKP5 / CS-C24BKP CU-C24BKP6