Air Circulation Mode Operation Time Diagram
Standard for Determining Operation Mode
8.3. Air Circulation Mode Operation
•
When the temperature near the ceiling reaches the setting temperature, Air Circulation Mode operation commences at low
airflow volume. It stops when the temperature drops to 2°C below the setting temperature.
8.4. Automatic Mode Operation
•
Indoor fan operates at SLo fan speed for 20 seconds.
•
After judging indoor air temperature, the operation mode is determined and operation continued at the mode determined.
•
After the operation mode has been determined, the mode does not change. However, Soft Dry mode operation includes
Cooling mode operation.
•
Room temperature adjustment.
The following are added to the setting temperature specified as above.
•
The mode judging temperature and standard setting temperature can be increased by 2°C, by open the circuit of JX1 at indoor
electronic controller.
23
CS-C18BKP CU-C18BKP5 / CS-C18BKP CU-C18BKP6 / CS-C24BKP CU-C24BKP5 / CS-C24BKP CU-C24BKP6