EasyManuals Logo

Panasonic CS-C18BKP Service Manual

Panasonic CS-C18BKP
79 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #62 background imageLoading...
Page #62 background image
13.1.1. Relationship between the condition of the air conditioner and pressure and
electric current
Cooling Mode
Condition of the air
conditoner Low Pressure High Pressure Electric current during operation
Insufficient refrigerant (gas
leakage)
Clogged capillary tube or
Strainer
Short circuit in the indoor unit
Heat radiation deficiency of
the outdoor unit
Inefficient compression
Carry out the measurements of pressure, electric current, and temperature fifteen minutes after an operation is started.
13.1.2. Diagnosis methods of a malfunction of a compressor
Nature of fault Symptom
Electric current during operation becomes approximately 20% lower than the normal value.
Insufficient compressing of a compressor
The discharge tube of the compressor becomes abnormally hot (normally 70 to 90°C).
The difference between high pressure and low pressure becomes almost zero.
Electric current reaches a high level abnormally, and the value exceeds the limit of an
ammeter. In some cases, a breaker turns off.
Locked compressor
The compressor has a humming sound.
62
CS-C18BKP CU-C18BKP5 / CS-C18BKP CU-C18BKP6 / CS-C24BKP CU-C24BKP5 / CS-C24BKP CU-C24BKP6

Other manuals for Panasonic CS-C18BKP

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Panasonic CS-C18BKP and is the answer not in the manual?

Panasonic CS-C18BKP Specifications

General IconGeneral
BrandPanasonic
ModelCS-C18BKP
CategoryAir Conditioner
LanguageEnglish

Related product manuals