Page #64 background image
240V Outdoor Temp. (°C)
Indoor wet
bulb temp.
30 35 40 46
TC SHC IP TC SHC IP TC SHC IP TC SHC IP
17.0°C 6.80 5.15 2.42 6.35 4.94 2.60 5.90 4.75 2.78 5.37 4.51 3.00
19.0°C 6.85 2.64
19.5°C 7.46 5.39 2.46 6.97 5.18 2.65 6.49 4.99 2.84 5.90 4.75 3.06
22.0°C 8.13 5.59 2.51 7.60 5.38 2.70 7.07 5.19 2.89 6.43 4.95 3.11
230V Outdoor Temp. (°C)
Indoor wet
bulb temp.
30 35 40 46
TC SHC IP TC SHC IP TC SHC IP TC SHC IP
17.0°C 6.97 5.29 2.38 6.52 5.07 2.56 6.06 4.87 2.74 5.51 4.63 2.96
19.0°C 7.03 2.60
19.5°C 7.66 5.54 2.43 7.16 5.32 2.61 6.66 5.12 2.79 6.05 4.87 3.01
22.0°C 8.34 5.74 2.47 7.80 5.52 2.66 7.25 5.33 2.84 6.59 5.08 3.07
220V Outdoor Temp. (°C)
Indoor wet
bulb temp.
30 35 40 46
TC SHC IP TC SHC IP TC SHC IP TC SHC IP
17.0°C 6.97 5.29 2.21 6.52 5.07 2.37 6.06 4.87 2.54 5.51 4.63 2.74
19.0°C 7.03 2.41
19.5°C 7.66 5.54 2.25 7.16 5.32 2.42 6.66 5.12 2.59 6.05 4.87 2.79
22.0°C 8.34 5.74 2.29 7.80 5.52 2.46 7.25 5.33 2.63 6.59 5.08 2.84
TC - Total Cooling Capacity (kW) Indoor 27°C/19°C
SHC - Sensible Heat Capacity (kW) Outdoor 35°C/24°C
IP - Input Power (kW)
64
CS-C18BKP CU-C18BKP5 / CS-C18BKP CU-C18BKP6 / CS-C24BKP CU-C24BKP5 / CS-C24BKP CU-C24BKP6

Other manuals for Panasonic CS-C18BKP

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Panasonic CS-C18BKP and is the answer not in the manual?

Panasonic CS-C18BKP Specifications

General IconGeneral
BrandPanasonic
ModelCS-C18BKP
CategoryAir Conditioner
LanguageEnglish

Related product manuals