8.4. Operation Control
(For 8.4.1. to 8.4.7. information applies only to Cooling and Soft Dry Operation)
8.4.1. Restart Control (Time Delay Safety Control)
When the thermo-off temperature (temperature which compressor stops to operate) is reached during:-
Cooling operation - the compressor stops for 3 minutes (minimum) before resume operation.
Soft Dry operation - the compressor stops for 6 minutes (minimum) before resume operation.
If the operation is stopped by the remote control, the compressor will not turn on within 3 minutes from the moment operation
stop, although the unit is turn on again within the period.
This phenomenon is to balance the pressure inside the refrigerant cycle.
8.4.2. 7 Minutes Time Save Control
The compressor will start automatically if it has stopped for 7 minutes and the intake air temperature falls between the
compressor ON temperature (A) and compressor OFF temperature (B) during the period.
This phenomenon is to reduce the built up humidity inside a room.
8.4.3. 60 Seconds Forced Operation
Once the air conditioner is turned on, the compressor will not stop within 60 seconds in a normal operation although the intake
air temperature has reached the thermo-off temperature. However, force stop by pressing the OFF/ON operation button at the
remote control is permitted.
The reason for the compressor to force operate at minimum 60 seconds is to allow the refrigerant oil run in a full cycle and
return back to the outdoor unit.
8.4.4. Anti-Freezing Control
If the temperature of the indoor heat exchanger falls below 2°C continuously for 4 minutes or more, the compressor turns off.
The fan speed setting remains the same.
This phenomenon is to protect the indoor heat exchanger from freezing and to prevent higher volume of refrigerant in liquid form
returning to the compressor.
Compressor will restart again when the indoor heat exchanger temperature rises to 10°C (Recovery).
Restart control (Time Delay Safety Control) will be applied in this Control if the recovery time is too short.
20
CS-C18DKD CU-C18DKD / CS-C24DKD CU-C24DKD