(Re-installation)
1. Remove the cap nut from 3-way valves.
Remove the cap nut from 3-way valves after carefully
checked whether the piping connection was properly
and certainly done.
2. Confirm that the valve in both 3-way valves are set to
the CLOSED position.
3. Connect the gas cylinder to the liquid-side (high-
pressure) 3-way valve and the charge set to the gas
side (low-pressure) 3-way valve.
Remove the flare nut from the service port to connect
the charge set and gas cylinder.
Close the valves on the gas cylinder and charge set.
4. Air purging.
Open the valve on the gas cylinder.
Open the valve on the charge set, discharge for three
seconds and wait for one minute. Repeat this three
times.
5. Check for gas leakage.
Check the flare connections for gas leakage.
6. Discharge the refrigerant.
Close the valve on the gas cylinder and discharge the
refrigerant until the gauge indicates 3 to 5 kg/cm
2
G.
7. Disconnect the charge set and the gas cylinder.
8. Mount the valve stem cap nuts and the flare nuts for
service port onto the 3-way valves.
9. Mount the cap nut and service port nut onto the 3-way
valves.
Be sure to use a torque wrench (CWHAD-9211) to
tighten the service port nut.
Be sure to check for gas leakage.
11.2.1. Re-air purging
Procedure:
50
CS-C9DKZW CU-2C18DKH / CS-C9DKZW CU-3C20DKH