(No refrigerant in the refrigeration cycle)
1. Connect the vacuum pump to the charge set’s centre
hose.
2. Evacuation for approximately one hour.
Confirm that the gauge needle has moved toward -76
cmHg [vacuum of 4 mmHg or less].
3. Close the valve (Lo side) on the charge set, turn off the
vacuum pump, and confirm that the gauge needle does
not move (approximately 5 minutes after turning off the
vacuum pump).
4. Disconnect the charge hose from the vacuum pump.
Vacuum pump oil.
If the vacuum pump oil becomes dirty or depleted,
replenish as needed.
11.3. Evacuation
Procedure:
52
CS-C9DKZW CU-2C18DKH / CS-C9DKZW CU-3C20DKH