36
12.1.5 Automatic Operation
• This mode can be set using remote control and the operation is decided by remote control setting temperature,
remote control operation mode and indoor intake air temperature.
• During operation mode judgment, indoor fan motor (with speed of Lo-) is running for 30 seconds to detect the
indoor intake air temperature.
• Every 10 minutes, the indoor temperature is judged.
• For the 1st judgment
o If indoor intake temperature - remote control setting temperature 2°C, COOL mode is decided.
o If -2°C indoor intake temperature - remote control setting temperature < 2°C, DRY mode is decided.
o If indoor intake temperature - remote control setting temperature < -2°C, HEAT mode is decided.
Heat Dr
Cool
-6 -5 -4 -3 -1 0 4 653
2
1
-2
• For the 2nd judgment onwards
o If indoor intake temperature - remote control setting temperature 3°C, if previous operate in DRY mode,
then continue in DRY mode. otherwise COOL mode is decided.
o If -2°C indoor intake temperature - remote control setting temperature < 3°C, maintain with previous mode.
o If indoor intake temperature - remote control setting temperature < -2°C, HEAT mode is decided.
Heat
Maintain
current mode
Cool
/Dry
-6
-5
-4
-3 -2 -1
0 4 652 31
12.1.6 Fan Operation
• Fan Operation is used to circulate air in a room.
• During operation, indoor fan run continuously but outdoor fan and compressor stop.
• Temperature setting is not applicable.
12.2 Indoor Fan Motor Operation
A. Basic Rotation Speed (rpm)
i. Manual Fan Speed
[Cooling, Dry, Fan]
• Fan motor’s number of rotation is determined according to remote control setting.
Remote control O O O O O
Tab Hi Me+ Me Me- Lo
[Heating]
• Fan motor’s number of rotation is determined according to remote control setting.
Remote control O O O O O
Tab SHi Me+ Me Me- Lo