EasyManua.ls Logo

Panasonic CS-CE9PKE - Timer Control

Panasonic CS-CE9PKE
98 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
38
12.4.1 Vertical Airflow
Vane Angle (°)
Operation Mode Airflow Direction
1 2 3 4 5
A 10
B 43.8
Auto Heat Exchanger
Temperature
C 21.2
Heating
Manual 10 21.2 32.5 43.8 55
Auto 10 ~ 40
Cooling and Fan
Manual 10 17.5 25 32.5 40
Auto 10 ~ 40
Soft Dry
Manual 10 17.5 25 32.5 40
1 Automatic vertical airflow direction can be set using remote control; the vane swings up and down within the
angles as stated above. For heating mode operation, the angle of the vane depends on the indoor heat
exchanger temperature as Figure 1 below. It does not swing during fan motor stop. When the air conditioner
is stopped using remote control, the vane will shift to close position.
2 Manual vertical airflow direction can be set using remote control; the angles of the vane are as stated above
and the positions of the vane are as Figure 2 below. When the air conditioner is stopped using remote control,
the vane will shift to close position.
135°C
Close position
Side View
Figure2
58°C
50°C
30°C
C
B
A
IndoorHeat
ExchangerTemperature
Figure1
36°C
1
2
3
4
5
12.4.2 Horizontal Airflow
The horizontal airflow direction louvers can be adjusted manually by hand.
12.5 Timer Control
There are 2 sets of ON and OFF timer available to turn the unit ON or OFF at different preset time.
If more than one timer had been set, the upcoming timer will be displayed and will activate in sequence.
12.5.1 ON Timer Control
ON timer 1 and ON timer 2 can be set using remote control, the unit with timer set will start operate earlier than
the setting time.
This is to provide a comfortable environment when reaching the set ON time.
60 minutes before the set time, indoor (at fan speed of Lo-) and outdoor fan motor start operate for 30 seconds to
determine the indoor intake air temperature and outdoor air temperature in order to judge the operation starting
time.
From the above judgment, the decided operation will start operate earlier than the set time as shown below.
Indoor int
a
ke air
temperature (
o
C)
Outdoor air
temperature (
o
C)
30
30 35
Cooling/Soft Dry/Fan
(
o
C)
10 min
15 min
5 min
25
Indoor int
a
ke air
temperature (
o
C)
Outdoor air
temperature (
o
C)
15
05
Heating
(
o
C)
30 min
25 min
35 min
5

Table of Contents

Other manuals for Panasonic CS-CE9PKE

Related product manuals